      HF-Ri TD 1 35/49/80 TL5 E+ 195-240V
      HF-Ri TD 1 35/49/80 TL5 E+ 195-240V
      HF-Regulator Intelligent Touch DALI for TL5/TL-D/PL-L lamps

      HF-Ri TD 1 35/49/80 TL5 E+ 195-240V

      Order code: 66207500

      Full product code: 871829166207500

    Specifications Show all

    General information
    Application Code
    E+
    Type Version
    mk2
    Lamp Type
    TL5
    Number of Lamps
    1 piece/unit
    Number of Products on MCB (16A Type B) (Nom)
    18
    Automatic Restart
    Yes
    Operating and electrical
    Input Voltage
    195-240 V
    Input Frequency
    50 to 60 Hz
    Operating Frequency (Max)
    110 kHz
    Operating Frequency (Min)
    45 kHz
    Ignition Method
    Warm Start
    Crestfactor (Max)
    1.7
    Power Factor 100% Load (Nom)
    0.95
    Ignition Time (Max)
    1 s
    Mains Voltage Performance (AC)
    -8%-+6%
    Mains Voltage Safety (AC)
    -10%-+10%
    Earth Leakage Current (Max)
    0.5 mA
    Inrush Current Width
    0.25 ms
    Standby Power Consumption (Max)
    0.25 W
    Ballast Factor (Nom)
    1
    Power Losses (Nom)
    4.5 W
    Inrush Current Peak (Max)
    28 A
    Efficiency at full load [%]
    92.6 %
    Wiring
    Connector Type Input Terminals
    WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
    Cable Capacity Output Wires Mutual (Max)
    200 pF
    Connector Type Output Terminals
    WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
    Connector Type Control Input Terminals
    WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
    Wire Striplength
    8.0-9.0 mm
    Dual Fixture Master/Slave
    Yes  [ Master/Slave operation possible]
    Control Input Terminal Cross Section
    0.50-1.00 mm²
    Input Terminal Cross Section
    0.50-1.00 mm²
    Output Terminal Cross Section
    0.50-1.00 mm²
    Auto Insert (ALF/ADS) Wire Cross Section
    0.75 mm²
    Cable Capacity Output Wires to Earth (Max)
    200 pF
    System characteristics
    Rated Lamp Power on TL-D
    -
    System Power on TL-D
    -
    Lamp Power on TL-D
    -
    Power Loss on TL-D
    -
    Rated Lamp Power on PL-L
    80 W
    System Power on PL-L
    81.9 W
    Lamp Power on PL-L
    76.3 W
    Power Loss on PL-L
    5.6 W
    Rated Lamp Power on TL5
    35/49/80 W
    System Power on TL5
    38.6/55.2/81.4 W
    Lamp Power on TL5
    35.9/51/75.6 W
    Power Loss on TL5
    2.7/4.2/5.8 W
    Rated Lamp Power on TL5 ECO
    32/45/73 W
    System Power on TL5 ECO
    36.3/48.7/79 W
    Lamp Power on TL5 ECO
    32.8/45.2/73.6 W
    Power Loss on TL5 ECO
    3.5/5.4 W
    Temperature
    T-Ambient (Max)
    50 °C
    T-Ambient (Min)
    -25 °C
    T-Storage (Max)
    80 °C
    T-Storage (Min)
    -40 °C
    T-Case Lifetime (Max)
    75 °C
    T-Case Maximum (Max)
    75 °C
    Stable Lamp Operation Temperature
    15°C
    T-Ignition (Max)
    50 °C
    T-Ignition (Min)
    -25 °C
    Controls and dimming
    Control Interface
    TD
    Regulating Level Power
    1%-100%
    Control Input Protection
    Yes (Basic insulation)
    Mechanical and housing
    Housing
    L 359x30x21
    Emergency operation
    Battery Voltage Lamp Ignition
    198-254 V
    Battery Voltage Lamp Operation
    176-254
    Approval and application
    Energy Efficiency Index
    A1 BAT
    IP Classification
    IP 20  [ Ingress Protection 20]
    EMI 9 kHz ... 30 MHz
    EN55015
    EMI 30 MHz ... 1000 MHz
    EN 55022 Class B
    Safety Standard
    IEC 61347-2-3
    Performance Standard
    IEC 60929
    Quality Standard
    ISO 9000:2000
    Environmental Standard
    ISO 14001
    Harmonic Current Emission Standard
    IEC 61000-3-2
    EMC Immunity Standard
    IEC 61547
    Vibration Standard
    IEC68-2-6 F c
    Bumps Standard
    IEC 68-2-29 Eb
    Humidity Standard
    EN 61347-2-3 clause 11
    Approval Marks
    CE marking
    ENEC certificate
    VDE-EMV certificate
    Temperature Marking
    Yes
    Emergency Standard
    IEC 60598-2-22
    Hum And Noise Level
    Inaudible
    Product data
    Full product code
    871829166207500
    Order product name
    HF-Ri TD 1 35/49/80 TL5 E+ 195-240V
    EAN/UPC - Product
    8718291662075
    Order code
    66207500
    Numerator - Quantity Per Pack
    1
    Numerator - Packs per outer box
    12
    Material Nr. (12NC)
    913700695766
    Net Weight (Piece)
    0.261 kg
    Installation diagrams
    HF-Ri TD 1 35/49/80 TL5 E+ 195-240V
    HF-Ri TD 1 35/49/80 TL5 E+ 195-240V
    HF-Ri TD 1 14/21/24/39 TL5 E+
    HF-Ri TD 1 14/21/24/39 TL5 E+
    Downloads
    Leaflets
    Visuals

    Recently viewed

    • Отметнете продукт, за да го добавите
       
    • Отметнете продукт, за да го добавите
       
    • Отметнете продукт, за да го добавите
       
    Отметнете продукт, за да го добавите