Application Code | E+
|
Type Version | mk2
|
Lamp Type | TL5
|
Number of Lamps | 1
piece/unit
|
Number of Products on MCB (16A Type B) (Nom) | 39
|
Automatic Restart | Yes
|
Input Voltage | 195-240
V
|
Input Frequency | 50 to 60
Hz
|
Operating Frequency (Max) | 110
kHz
|
Operating Frequency (Min) | 45
kHz
|
Ignition Method | Warm Start
|
Crestfactor (Max) | 1.7
|
Power Factor 100% Load (Nom) | 0.95
|
Ignition Time (Max) | 1
s
|
Mains Voltage Performance (AC) | -8%-+6%
|
Mains Voltage Safety (AC) | -10%-+10%
|
Earth Leakage Current (Max) | 0.5
mA
|
Inrush Current Width | 0.18
ms
|
Standby Power Consumption (Max) | 0.25
W
|
Ballast Factor (Nom) | 1
|
Power Losses (Nom) | 3.8
W
|
Inrush Current Peak (Max) | 20
A
|
Efficiency at full load [%] | 93
%
|
Connector Type Input Terminals | WAGO 251 universal connector
[ Suitable for both automatic wiring (ALF and ADS) and manual wiring] |
Cable Capacity Output Wires Mutual (Max) | 200
pF
|
Connector Type Output Terminals | WAGO 251 universal connector
[ Suitable for both automatic wiring (ALF and ADS) and manual wiring] |
Connector Type Control Input Terminals | WAGO 251 universal connector
[ Suitable for both automatic wiring (ALF and ADS) and manual wiring] |
Wire Striplength | 8.0-9.0
mm
|
Dual Fixture Master/Slave | Yes
[ Master/Slave operation possible] |
Control Input Terminal Cross Section | 0.50-1.00
mm²
|
Input Terminal Cross Section | 0.50-1.00
mm²
|
Output Terminal Cross Section | 0.50-1.00
mm²
|
Auto Insert (ALF/ADS) Wire Cross Section | 0.75
mm²
|
Cable Capacity Output Wires to Earth (Max) | 200
pF
|
Rated Ballast-Lamp Power | 28-35-49-54 W
|
Rated Lamp Power on TL-D | 58
W
|
System Power on TL-D | 55.5
W
|
Lamp Power on TL-D | 52.2
W
|
Power Loss on TL-D | 3.3
W
|
Rated Lamp Power on PL-L | 55
W
|
System Power on PL-L | 54.6
W
|
Lamp Power on PL-L | 51.2
W
|
Power Loss on PL-L | 3.4
W
|
Rated Lamp Power on TL5 | 28/35/49/54
W
|
System Power on TL5 | 32.1/39.1/55.1/57.7
W
|
Lamp Power on TL5 | 29.4/36.4/51.6/54.8
W
|
Power Loss on TL5 | 2.7/3.0/3.5
W
|
Rated Lamp Power on TL5 ECO | 25/32/45/50
W
|
System Power on TL5 ECO | 29.4/33.1/49.1/54.2/
W
|
Lamp Power on TL5 ECO | 26.3/30.2/45.7/50.4
W
|
Rated Lamp Power on TL-D ECO | 51
W
|
System Power on TL-D ECO | 45.8
W
|
Power Loss on TL-D ECO | 3.1
W
|
Lamp Power on TL-D ECO | 42.7
W
|
Power Loss on TL5 ECO | 3.1/2.9/3.4/3.8/
W
|
T-Ambient (Max) | 50
°C
|
T-Ambient (Min) | -25
°C
|
T-Storage (Max) | 80
°C
|
T-Storage (Min) | -40
°C
|
T-Case Lifetime (Max) | 75
°C
|
T-Case Maximum (Max) | 75
°C
|
Stable Lamp Operation Temperature | 15°C
|
T-Ignition (Max) | 50
°C
|
T-Ignition (Min) | -25
°C
|
Control Interface | TD
|
Regulating Level Power | 1%-100%
|
Control Input Protection | Yes (Basic insulation)
|
Housing | L 359x30x21
|
Battery Voltage Lamp Ignition | 198-254
V
|
Battery Voltage Lamp Operation | 176-254
|
Energy Efficiency Index | A1 BAT
|
||
IP Classification | IP 20
[ Ingress Protection 20] |
||
EMI 9 kHz ... 30 MHz | EN55015
|
||
EMI 30 MHz ... 1000 MHz | EN 55022 Class B
|
||
Safety Standard | IEC 61347-2-3
|
||
Performance Standard | IEC 60929
|
||
Quality Standard | ISO 9000:2000
|
||
Environmental Standard | ISO 14001
|
||
Harmonic Current Emission Standard | IEC 61000-3-2
|
||
EMC Immunity Standard | IEC 61547
|
||
Vibration Standard | IEC68-2-6 F c
|
||
Bumps Standard | IEC 68-2-29 Eb
|
||
Humidity Standard | EN 61347-2-3 clause 11
|
||
Approval Marks | CE marking
|
ENEC certificate
|
VDE-EMV certificate
|
Temperature Marking | Yes
|
||
Emergency Standard | IEC 60598-2-22
|
||
Hum And Noise Level | Inaudible
|
Full product code | 871829166205100
|
Order product name | HF-Ri TD 1 28/35/49/54 TL5 E+ 195-240V
|
EAN/UPC - Product | 8718291662051
|
Order code | 66205100
|
Numerator - Quantity Per Pack | 1
|
Local code description | REATOR ELETRONICO FLUOR HF-RITD12854E++
|
Numerator - Packs per outer box | 12
|
Material Nr. (12NC) | 913700695666
|
Net Weight (Piece) | 0.261
kg
|