Application Code | EII
|
Type Version | mk1
|
Lamp Type | TL5
|
Number of Lamps | 1
piece/unit
|
Number of Products on MCB (16A Type B) (Nom) | 18
|
Automatic Restart | Yes
|
Input Voltage | 220 to 240
V
|
Input Frequency | 50 to 60
Hz
|
Ignition Method | Warm Start
|
Crestfactor (Max) | 1.7
|
Ignition Time (Max) | 5.0
s
|
Mains Voltage Performance (AC) | -8%-+6%
|
Mains Voltage Safety (AC) | -10%-+10%
|
Earth Leakage Current (Max) | 0.5
mA
|
Inrush Current Width | 0.35
ms
|
Constant Wattage Deviation | -2%/+2%
|
Ballast Factor (Nom) | 1.00
|
Power Losses (Nom) | 4.8-7.0
W
|
Inrush Current Peak (Max) | 20
A
|
Efficiency at full load [%] | 90.87
%
|
Connector Type Input Terminals | Insert
|
Cable Capacity Output Wires Mutual (Nom) | 70
pF
|
Connector Type Output Terminals | Insert
|
Cable Length Hot Wiring | 0.75
m
|
Wire Striplength | 8.0-9.0
mm
|
Input Terminal Cross Section | 0.50-1.00
mm²
|
Output Terminal Cross Section | 0.50-1.00
mm²
|
Cable Capacity Output Wires to Earth (Nom) | 70
pF
|
Rated Ballast-Lamp Power | 28-54 W
|
Rated Lamp Power on TL5 | 28/35/49/54
W
|
System Power on TL5 | 37.9/44.4/56.8/62.6
W
|
Lamp Power on TL5 | 30.9/39.8/52.6/57.8
W
|
Power Loss on TL5 | 7/4.6/4.2/4.8
W
|
T-Ambient (Max) | 50
°C
|
T-Ambient (Min) | -25
°C
|
T-Storage (Max) | 80
°C
|
T-Storage (Min) | -40
°C
|
T-Case Lifetime (Nom) | 75
°C
|
T-Case Maximum (Max) | 75
°C
|
T-Ignition (Max) | 50
°C
|
T-Ignition (Min) | -25
°C
|
Housing | L360x30x22
|
Nominal Light Output After 60 Seconds | 100% of EBLF
|
Battery Voltage Lamp Operation | 198-276
|
Emergency Ballast Lumen Factor (EBLF) (Nom) | 100
%
|
Nominal Light Output After 5 Seconds | 50% of EBLF
|
Energy Efficiency Index | A2 BAT
|
||
IP Classification | IP 20
[ Ingress Protection 20] |
||
EMI 9 kHz ... 30 MHz | EN55015
|
||
EMI 30 MHz ... 1000 MHz | EN 55022 Class B
|
||
Safety Standard | IEC 61347-2-3
|
||
Performance Standard | IEC 60929
|
||
Quality Standard | ISO 9000:2000
|
||
Environmental Standard | ISO 14001
|
||
Harmonic Current Emission Standard | IEC 61000-3-2
|
||
EMC Immunity Standard | IEC 61547
|
||
Vibration Standard | IEC68-2-6 F c
|
||
Bumps Standard | IEC 68-2-29 Eb
|
||
Humidity Standard | EN 61347-2-3 clause 11
|
||
Approval Marks | CE marking
|
ENEC certificate
|
VDE-EMV certificate
|
Temperature Marking | Yes
|
||
Emergency Standard | IEC 60598-2-22
|
||
Hum And Noise Level | Inaudible
|
Full product code | 871150091496530
|
Order product name | HF-Pi 1 28/35/49/54 TL5 EII 220-240V
|
EAN/UPC - Product | 8711500914965
|
Order code | 91496530
|
Numerator - Quantity Per Pack | 1
|
Numerator - Packs per outer box | 12
|
Material Nr. (12NC) | 913700624166
|
Net Weight (Piece) | 0.247